Water Or Steam Boiler Repair Laporte, Indiana
Remove Existing Relay Controls And Related Wiring As Needed.
Provide And Install New Relay Controls And Wiring As Needed To Operate The Existing Boiler And Existing Pumps With The Existing Thermostat Controls.
LAPORTE, IN
01-15-2021
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Drained Boiler System, Replaced Failed Reducing Valve And Added Isolation For Future Service As Part Of Proposal. Filled System To Approximately 12 PSIG Cold And Bled All Radiation. Cycled Boiler To Ensure Proper Operation And Unit Is Heating Properly At This Time. Boiler Cycles Off At 165° With A Pressure Of Approximately 19 PSIG.
LAPORTE, IN
12-31-2020
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For Boiler Leaking Water. Upon Arrival Found Evidence Of Relief Valve Dripping. Found System At 20 PSIG And 140°. Cycled Boiler To 180° And System Cycled Off At 23 PSIG. Suspect Reducing Valve To Have Slowing Filled The System. Replaced Reducing Valve And Added A Check Valve. Set Fill Reducing Valve To Approximately 12 PSIG And Observed The Boiler Cycle Off At 180° With A Pressure Of Approximately 19 PSIG. System Is Operating Properly At This Time.
LaPorte, IN
11-27-2020
Water Or Steam Boiler Repair Laporte, Indiana
Provide And Install A New Thermocouple.
LAPORTE, IN
11-24-2020
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For Bedroom Circulator Pump Leaking. Upon Arrival Found B&G Circulator Pump Serving Bedroom Zone Leaking During Operation. Client Requested Replacement Of The Two Remaining Circulator Pumps. Drained Boiler System, Replaced Two Client Provided Circulator Pumps, Bled Air From System And Cycled All Three Zones To Ensure Proper System Operation. Verified All Radiation Is Heating Properly And Observed Boiler Cycle Off At 180° With A Pressure Of Approximately Psi.
LaPorte, IN
11-20-2020
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call To Service Boiler System And Check For Odd Smell In Mechanical Room. Cleaned Burners, Cleaned Flame Sensor, Measured Igniter Resistance At 5 Ohms, Cleared Condensate Trap, Tested Relief Valve And Tested Fill Reducing Valve, Cleaned Inducer Signal Port And Cycled Boiler From All Four Zones To Ensure Proper Operation. Observed System Operate Properly And Cycle Off At 200° With A Pressure Of Approximately 21 PSIG. Inspected All Venting On Both Boiler And Water Heater And Performed A Carbon Monoxide Test In The Mechanical Room. Could Not Determine Where Cause Of Smell Is Originating. Recommend Client To Inspect Perimeter Drain System.
LaPorte, IN
10-19-2020
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call To Service Boiler System And Search For A Gas Leak. Upon Arrival Searched All Gas Fittings In The Home And Found Leak At Old Abandoned Gas Stove. Abandoned Gas Stove And All Supply Piping With A Cap At The Main Branch. Re-lit All Gas Appliances And Checked For Leaks. Serviced The Boiler System. Drained Expansion Tank, Oiled Circulator Pump, Cleaned Burners, Replaced Thermocouple, Replaced Relief Valve And Cycled Boiler To Ensure Proper Operation. System Is Heating Properly At This Time And Cycles Off At 180° With A Pressure Of Approximately 15 PSIG. Recommend Having Boiler System Serviced Annually For Preventative Maintenance Purposes.
LaPorte, IN
07-17-2020
Water Or Steam Boiler Repair Laporte, Indiana
Technician Invoice Notes: Call For Main Circulator Pump Leaking. Upon Arrival Found Failed Bearing Assembly In Main B&G Pump. Replaced Pump Assembly With New Taco Circulator And Cycled Boiler To Ensure Proper Operation. System Is Heating Properly At This Time. Recommend Having The Other Two Circulator Pumps Replaced Due To Noisy Operation And Having Boiler Serviced Annually For Preventative Maintenance Purposes.
LaPorte, IN
04-10-2020
Water Or Steam Boiler Repair Laporte, Indiana
Call For No Heat. Upon Arrival Found Boiler System With No Pressure And Not Operating. Pressurized Boiler And Boiler System Piping. Could Not Determine Any Leaks At This Time. After Further Investigation Found Failed Roll-out Safety Switch. Found Chimney Clean Out Cover Forced Open From Chimney Debri Which Allowed Boiler To Vent Into The Home And Burn Incorrectly. Boiler Sections Are Sooted To The Point Of Boiler Failure. Gathered Information To Provide An Estimate For A Replacement Boiler System. Client Will Receive The Estimate Via Email When Completed. Left Power To Wi-if Thermostat On For Remote Temperature Monitoring.
LaPorte, IN
03-26-2020